SBER1238

SBER1238 - REDUCER ELBOW, SOLDER FREE, 3/8" X 1/2"

SB1 Series Quick Connect Refrigerant Fittings are FLAME FREE, Tool FREE and Problem FREE! /they are available as couplers, (45 & 90°) elbows and flares for 1/4" to 7/8" copper tubing. No brazing, tools or nitrogen purge needed for installation.

Features/Benefits

  • Approved Refrigerants - R134a, R404A, R290, R407A, R600a, R507, R22, R410A, R32, R407C
  • Approved for Hard Soft Copper (Annealed): 1/4" - 7/8" Type ACR, L, K
  • Approved for Hard Drawn Copper: 1/4" - 7/8" Type ACR, M, L, K
  • UL Listed 207, SA #44910 SDTW(7)
  • Vibration Resistant Rating UL 1963
  • C3771 Brass Body
  • WARNING: Prop 65 info
Locate a Distributor Near You
Type: 90°
Connection Thread: None
Outside Diameter (Inch): 1.181
Length (Inch): 1.339
Connection Size (Inch): 0.375 x 0.500
O-Ring Material: Chloroprene
Fitting Material: C3771, Polycarbonate
Compatibility-Tubing Tolerance: ASTM B280, UNI EN 12735
Vacuum Pressure Capability: 30 Microns
Minimum Burst Pressure : 3600 PSI / 250 Bar
Maximum Rated Pressure (MRP): 870 PSI / 60 Bar
O-Ring Temperature: -40°F / 250°F (-40°C / 121°C)
Continuous Operating Temperature: 250°F / 121°C
Refrigerants
Glycol
Non-Potable Water
SDS Product Sheets Cross Reference Information
no entry no entry no entry

Manuals Application Sheets Software
SBER1238_man_001.pdf
SBER1238_app_001.pdf
no entry

No Cross Reference Available

Can SB1s be used with aluminum, steel or stainless steel tubing?: No, only copper to copper connections
What is the shelf life of the fittings?: The manufacturer sets the shelf life @ 30+ years
Do the fittings need to be insulated after an install?: Yes, just as you would with any other fitting where it would be subject to condensation.
What is the #1 cause of problems with the SB1 fittings ?: Not reading/following the installation instructions
The SBLM1458 depth gauge only goes up to 5/8” so how do I mark 3/4” & 7/8” tubing?: Part number SBLMDC3478 is a combo tool, combining both a depth gauge and a disconnect tool
Do SB1s need to be replaced when retrofitting to a lower GWP refrigerant?: Yes. The compression set of the super neoprene o?rings may be compromised when transitioning from one refrigerant to another. Always install new fittings.
Can the fittings be removed and reinstalled on the same spot of tubing?: The fitting can be installed onto the same spot if the tube is properly sanded and cleaned, removing any etch marks, or replace onto a clean section of tubing.
What is the warranty on SB1 fittings?: A 5?year limited warranty policy which is available upon request.